Floor-ceiling FORT - RU0NF24ABE

ROVER FORT floor-ceiling indoor units are perfect for rooms without false ceiling and rooms of complex form. The indoor unit can be installed on the floor near the wall or under the ceiling.

Comfortable airflow. When the air conditioner is installed on the floor the air flow is directed upwards. Underceiling installation is horizontally, along the ceiling. This options allows distributing the cooled air evenly throughout the room and providing maximum comfort.

Functions and operating modes

  • Auto restart
  • Comfortable sleep
  • Automatic operation
  • Warm start
  • Timer setting
  • Self-diagnosis
  • Volumetric air flow
  • Digital display
  • Intelligent defrost
  • Fireproof electrical box
  • Low temperature cooling

Technical parameters

Model complete set RU0NF24ABE
indoor unit RU0NF24ABE/I
outdoor unit RU0NU24AAE/O
Capacity cooling kW 7.032
heating 7.62
Power supply ph/V/Hz 1/~(220±10%)/50
Rated power input cooling kW 2.63
heating 2.45
Operating current cooling A 12.62
heating 11.76
SEER/SCOP 2.67/3.11
Energy class D/D
Air flow (max.) м3/h 1 250/1 050/900
Noise level indoor unit dB(A) 44/48/53
outdoor unit 60
Refrigerant type R410А
Refrigerant charge* kg 2.0
Parameters of refrigerant pipes pipe diameter liq. 3/8''
gas 5/8''
length (max) м 25
height difference (max) 15
Drain pipe (outside diameter) mm ø25
Air switch** nominal current A 32
Power cable (to IDU) n×мм² 3×2.5
Power cable (to ODU) -
Interblock cable 3×2.5+3×1.0+2×0.2
Dimensions
(width × height × depth)
indoor unit mm 1 068×675×235
outdoor unit 890×673×342
Package dimensions
(width × height × depth)
indoor unit mm 1 145×755×313
outdoor unit 995×740×398
ODU installation dimensions mm 663×348
Weight (net / gross) indoor unit kg 24.6/29.8
outdoor unit 52.9/55.9

 

* The amount of freon is indicated for the pipe length of no more than 5 m. With an increase of the pipe length, it is necessary to charge the additional refrigerant at the rate of 15 g per 1 m for the 1/4″liquid pipe and 30 g per 1 m for the 3/8″liquid pipe.

** Cut-off current is not less than 7 In (In - rated current), leakage current is not more than 30mA, shutdown characteristic is «C». It is allowed to install the circuit breaker and RCD with the same capacity in series.

The table shows data for temperature conditions in accordance with ISO 5151-94:
- cooling mode inside 27 °C (DB)/19 °C (WB), outside 35 °C (DB)/24 °C (WB)
- heating mode inside 20 °C (DB)/15 °C (WB), outside 7 °C (DB)/6°C (WB)